Sized to fit within the generator footprint
The Florida Department of Environmental Protection (FDEP) FS-62-762 specifies the requirements for aboveground (sub base) generator fuel tanks installed in Florida. more information
The National Fire Protection Association (NFPA-37) specifies the maximum allowable capacity of an indoor fuel tank supplying a standby generator set. more information
|
Maximum Fuel Tank Capacity at the Height
(within generator footprint)
|
Fuel Consumption (GPH)@
|
|
Model
|
12" High Tank
|
18" High Tank
|
24" High Tank
|
30" High Tank
|
50% Load |
75% Load |
100% Load
|
|
20REOZJB
|
55
|
90
|
125
|
160
|
1.4
|
1.9
|
2.4
|
|
20REOZJB
Housed
|
70
|
110
|
150
|
200
|
1.4
|
1.9
|
2.4
|
|
30REOZJB
|
55
|
90
|
125
|
160
|
1.7
|
2.4
|
3.1
|
|
30REOZJB
Housed
|
70
|
110
|
150
|
200
|
1.7
|
2.4
|
3.1
|
|
40REOZJB
|
55
|
90
|
125
|
160
|
2.0
|
2.7
|
3.4
|
|
40REOZJB
Housed
|
70
|
110
|
150
|
200
|
2.0
|
2.7
|
3.4
|
|
50REOZJB
|
65
|
105
|
145
|
195
|
2.6 |
3.6
|
4.6
|
|
50REOZJB
Housed
|
82
|
130
|
180
|
230
|
2.6 |
3.6
|
4.6
|
|
60REOZJB
|
65
|
105
|
145
|
195
|
2.8
|
3.9
|
5.1
|
|
60REOZJB
Housed
|
82
|
130
|
180
|
230
|
2.8
|
3.9
|
5.1
|
|
80REOZJC
|
80
|
125
|
175
|
220
|
4.1
|
5.9
|
7.6
|
|
80REOZJC
Housed
|
100
|
160
|
220
|
280
|
4.1
|
5.9
|
7.6
|
|
100REOZJC
|
80 |
125 |
175 |
220 |
5.0 |
6.3 |
8.1 |
|
100REOZJC
Housed
|
100 |
160 |
220 |
280 |
5.0 |
6.3 |
8.1 |
|
135REOZJC
|
102 |
164 |
225 |
285 |
5.5 |
8.1 |
10.6 |
| 150REOZJC |
102 |
164 |
225 |
285 |
6.3 |
8.9 |
12.0 |
| 180REOZJC |
102 |
164 |
225 |
285 |
6.9 |
10.0 |
13.2 |
| 200REOZJC |
135 |
215 |
310 |
390 |
7.8 |
11.0 |
14.9 |
| 230REOZDD |
165 |
265 |
385 |
465 |
10.8 |
15.5 |
20.2 |
| 250REOZDD |
165 |
265 |
365 |
465 |
11.5 |
17.0 |
21.1 |
| 275REOZDD |
165 |
265 |
365 |
465 |
12.6 |
18.7 |
23.3 |
| 300REOZDD |
165 |
265 |
365 |
465 |
13.7 |
20.2 |
25.4 |
| 350REOZDD |
175 |
280 |
385 |
490 |
14.6 |
21.4 |
27.0 |
|
400REOZDD
|
175 |
280 |
385 |
490 |
16.6 |
24.7 |
31.9 |
|
450REOZDD
|
175 |
280 |
385 |
490 |
18.2 |
26.5 |
34.6 |
| 500REOZVB |
180 |
285 |
395 |
500 |
18.0 |
26.8 |
36.8 |
| 650REOZDB |
255 |
385 |
535 |
630 |
23.8 |
34.9 |
45.8 |
| 750REOZDB |
255 |
385 |
535 |
630 |
26.8 |
39.5 |
51.8 |
| 800REOZDB |
325 |
520 |
650 |
840 |
30.8 |
45.6 |
59.6 |
| 900REOZDB |
325 |
520 |
650 |
840 |
33.1 |
49.0 |
64.1 |
| 1000REOZDB |
325 |
520 |
650 |
840 |
36.5 |
53.5 |
70.6 |
|
1350REOZDB
|
530* |
740* |
1060* |
1380* |
50.0 |
71.1 |
92.1 |
|
1500REOZDB
|
560* |
830* |
1185* |
1540* |
54.7 |
78.3 |
102.9 |
|
1820REOZDB
|
610* |
900* |
1290* |
1675* |
66.4 |
95.0 |
123.0 |
|
2000REOZDB
|
610* |
900* |
1290* |
1675* |
72.4 |
104.6 |
137.4 |
|
2500REOZD
|
--- |
1400* |
1990* |
2580* |
93.2 |
133.4 |
171.1 |
|
2800REOZD
|
--- |
1400* |
1990* |
2580* |
102.8 |
148.5 |
191.5 |
* Add 5" to tank height for support crossmembers
Generator Installed Height


|
Model
|
Floor to Top of Silencer
|
|
20-230 kW
|
Inches
|
|
20REOZJB
|
108.50
|
|
30REOZJB
|
108.50
|
|
40REOZJB
|
108.50
|
|
50REOZJB
|
129.67
|
|
60REOZJB
|
129.67
|
|
80REOZJC
|
129.67
|
|
100REOZJC
|
129.67
|
|
135REOZJC
|
125.21
|
|
150REOZJC
|
125.21
|
|
180REOZJC
|
125.21
|
|
200REOZJC
|
128.54
|
|
230-500 kW
|
|
230REOZDD
|
144.80
|
|
250REOZDD
|
144.80
|
|
275REOZDD
|
144.80
|
|
300REOZDD
|
144.80
|
|
350REOZDD
|
147.82
|
|
400REOZDD
|
147.82
|
|
450REOZDD
|
157.82
|
|
500REOZVB
|
144.54
|
|
650-1000 kW
|
|
650REOZDB
|
138.48
|
|
750REOZDB
|
138.48
|
|
800REOZDB
|
148.50
|
|
900REOZDB
|
148.50
|
|
1000REOZDB
|
154.70
|
|
1350-2800 kW
|
|
1350REOZDB
|
192.29
|
|
1500REOZDB
|
182.79
|
|
1820REOZDB
|
183.54
|
|
2000REOZDB
|
183.54
|
|
2500REOZD
|
210.35
|
|
2800REOZD
|
210.35
|
| These dimensions are maximum installed height including silencer, spring isolators, flex and standard 30" H fuel tank. |
Discuss Diesel Sub-Base Fuel Tanks with a TAW Specialist: 800-456-9449.
Email: PowerSystems@tawinc.com