TAW Power Systems

 

 

Kohler Generators:  Technical Data   


► DECREMENT CURVES - Need a decrement curve for the generator your specifying?

Specifying a generator on a job that requires circuit breaker coordination and need the alternator decrement/damage curve, machine reactance and/or alternator time constants? Contact TAW Power Systems and we will provide the information for the alternator you're using.

Hints to make coordination easier.                                                                    
  1. Specify/use an oversized alternator on the genset. This provides more available fault current to work with and also moves the thermal damage curve farther out (higher) on the amperage axis giving more time/power to trip downstream breakers.
  2. Specify/use the Kohler DEC 550 controller. The DEC 550 controller has the thermal damage curve of the alternator you specify programmed into it’s microprocessor and is designed to remove excitation and shut down the genset just prior to the specific alternator’s thermal damage point i.e. maximum available power right up to the thermal damage point.
  3. If possible, size branch circuits being fed from the generator at 50% or less than the ampere capacity of the generator main circuit breaker; this may not than the ampere capacity of the generator main circuit breaker; this may not always be possible, but if you can, do it. The smaller the downstream breakers are with respect to the generator main breaker the greater the incidence of their tripping before the main breaker.

 

► GENERATOR SET RATINGS - Standby? Continuous? How are generator sets rated?  Kohler's TIB-101 explains it.

 

► GENERATOR SET OUTPUT - How many amps will the generator set put out?

 

 

Generator

 

Generator

 

Generator

 

Amps @

 

Amps @

 

Amps @

 

Amps @

 

Output KW

 

Output KVA

 

Output KVA

 

120/240 VAC

 

120/240 VAC

 

120/208 VAC

 

277/480 VAC

 

 

1 phase

 

3 phase

 

1 phase

 

3 phase

 

3 phase

 

3 phase

20

20

25

83.3

60.2

69.4

30.1

30

30

37.5

125

90.3

104

45.1

40

40

50

166.6

120.4

138.9

60.2

50

50

62.5

208.3

150.5

173.6

75.2

60

60

75

250

180.6

208.4

90.3

80

80

100

333.3

240.8

277.9

120.4

100

100

125

417

301

347

150

125

NA

156.25

NA

376

434

188

150

NA

187.50

NA

451

520

226

180

NA

225

NA

541

625

271

200

NA

250

NA

601

694

301

230

NA

287.5

NA

692

798

346

250

NA

312.5

NA

752

867

376

275

NA

343.75

NA

827

954

413

300

NA

375

NA

902

1041

451

350

NA

437.5

NA

1052

1214

526

400

NA

500

NA

1203

1388

601

450

NA

562.5

NA

1353

1561

677

500

NA

625

NA

1504

1735

752

600

NA

750

NA

1804

2082

902

750

NA

937.5

NA

2255

2602

1128

800

NA

1000

NA

NA

NA

1203

900

NA

1125

NA

NA

NA

1353

1000

NA

1250

NA

NA

NA

1504

1250

NA

1562.5

NA

NA

NA

1879

1500

NA

1875

NA

NA

NA

2255

1750

NA

2187.5

NA

NA

NA

2631

2000

NA

2500

NA

NA

NA

3007


 

► Motor Starting - Generator sets are often sized/specified based on the motor loads they are required to start and run.  A motor typically requires 4-7 times the running current to start it.  An important characteristic of a generator is its motor starting (SKVA) capability at 15% maximum instantaneous voltage dip (VD).   Check out the motor starting SKVA @ 15% VD of the alternators supplied on Kohler generator sets.


 

 

 

Register  Login